| Power Supply | 10..40 Vdc; 19..28 Vac |
| Power consumption | Max 1 W |
| Battery type and lifetime | Lithium with variable autonomy from 12 to 36 months |
| Status Indicators | Power supply Rx-Tx serial communications Sensors assigned Sensors in error |
| Protection degree | IP20 |
| Operating temperature | -20..+70°C |
| Connections | Screw terminals, removable 7-way screw, 5mm pitch Screw terminals, removable 2-way screw, 5mm pitch Ethernet connector |
| Communication | Nr 1 Fast Ethernet 100 Tx port, RJ45 front. Nr 1 RS232 / RS485 serial port switchable, baud rate max 115k on connector |
| Connectivity | Up to 8 TCP-IP Clients Max 128 Modbus RTU/ASCII Slave Nodes |
| Supported protocols | ModBUS TCP-IP, ModBUS RTU |
| Dimension (WxHxD) | 53.3 x 90 x 32.2 mm |
| Weight | 80 g |
| Housing | PC / ABS self-extinguishing UL94-V0 |
| Installation | On IEC EN 60715 DIN rail or wall-mounted |
| Certification | CE |
| Standards | ETSI EN 301 489-1 v.2.2.3, ETSi EN 301 409-3 v.2.1.1, EN 60950 |
| WIRELESS | |
| Radio Technology | LoRa |
| Minimum Measurement Interval | 30 seconds |
| Security | AES 128bit |
| Frequency | Frequency Band: 865-865 MHz, Nominal Frequency: 863.110 MHz, Bandwidth 25 KHz, Max Power +14 DBm |
| Sensitivity | Up to -146 dBm |
| Power | +14 dBm |
| Max Number of coupled sensors | 32 |
| SETTINGS & ADVANCED FUNCTIONS | |
| DIP switch | Yes |
| Webserver | Yes |
| SDD (Seneca Discovery Device) | Yes |
| Firmware Update | via Web Server |
| Advanced Diagnostics | Yes |