Cart  

No products

0,00 € Shipping
0,00 € Total

Prices are tax excluded

Cart Check out

protection relays MV and HV

New products

  • VE794600

    VE794600

    ENERGY-230 Wi-Fi ENERGY METER

    104,29 €

All new products

NM10

MULTIFUNCTION PROTECTION FOR SMALL/MEDIUM SIZE MOTORS (BASE)

More details...

Price on request

NM10

The relay type NM10 can be used for protection of medium size motors in MV and LV systems powered through lines of:
• any length in solidly or low resistance grounded systems
• small length in ungrounded or Petersen coil and/or high resistance grounded systems

Applications
• Motor
Protection functions
• Pt100 thermometric probes (26)
• Phase undercurrent (37)
• Negative sequence overcurrent (46)
• Thermal image (49)
• Phase overcurrent (50/51)
• Residual overcurrent (50N/51N)
• Locked rotor (51LR(48)/14)
• Maximum number of starting (66)
• High impedance restricted earth fault (87NHIZ)
• Breaker failure (BF)
Monitoring and control functions
• CB diagnostic
• Cold Load Pickup (CLP)
• CTs monitoring (74CT)
• Digital Fault recording (DFR)
• Fault and event logging (SER & SFR)
• Logic selectivity
• Multiple setting profiles
• Programmable Logic Controller
• Self-test
• Trip circuit supervision (74TCS)
Hardware
• 2 binary inputs + 6 output relays + 8 LEDs
• Auxiliary power supply 110-230 Vac/dc
• Auxiliary power supply 24-48 Vac/dc
• Flush, projecting, projecting, rack, with separate MMI
• Network module with Ethernet FX port (optical fiber)
• Network module with Ethernet TX port (copper RJ45) + RS485 port
• Nominal current 1/5 A selectable by DIP-switch
• RS485 port (unavailable with Ethernet FX port)
• Standard CT amperometric inputs 1/5 A
Communication
• Modbus RTU RS232 protocol
• Modbus RTU RS485 / IEC 870-5-103 / DNP3 protocol
• Modbus TCP/IP protocol (network board must be provided)

  • application MOTOR
  • ANSI protection Locked rotor (51LR(48)/14)|Residual overcurrent (50N/51N)|Pt100 thermometric probes (26)|Phase undercurrent (37)|Thermal image (49)|Phase overcurrent (50/51)|Maximum number of starting (66)|Breaker failure (BF)|High impedance restricted earth fault (87NHIZ)|Negative sequence overcurrent (46)

21 other products in the same category :