Cart  

No products

0,00 € Shipping
0,00 € Total

Prices are tax excluded

Cart Check out

Rogowski /5A

New products

All new products

IN-LO-RS-3000-05A

4000 A Rogowski Coil with /5A Output, 150 mm Diameter, 2 Meter Cable

More details...

Availability : stock

IN-LO-RS-4000-05A

723,64 €

4000 A Rogowski Coil with /5A Output, 150 mm Diameter, 2 Meter Cable

The flexible Rogowski coil current sensor is used to measure alternating current (AC), especially at high currents. Thanks to its flexibility, it can be used to measure current in conductors with large diameters, irregular shapes, or in tight spaces between conductors (for example, when a traditional current clamp or current transformer cannot measure, the flexible Rogowski coil provides a convenient solution).
Rogowski coils are known for their inherent advantages, including high linearity, a wide frequency range, and immunity to magnetic saturation.
The non-invasive design ensures easy installation without requiring direct electrical contact or modification of the primary circuit.


Applications

  • Secondary distribution substations
  • Monitoring of distribution transformers
  • BESS connection to utility meter
  • Monitoring of PV installations
  • Phasor Measurement Units (PMU)
  • Commercial and industrial buildings
  • Metering and submetering
  • Demand response (DR)
  • Distribution system equipment

Standards

  • IEC 61010-1: 2010
  • IEC 61010-2-32: 2012
  • IEC 61869-10: 2017
  • UL 61010-1: 2012

Electrical Specifications

Operating frequency: 50–60 Hz
Supply voltage: ±8V–±12V DC, ≥50W
Burden: <0.1 Ω
Frequency range: 10 Hz–1 kHz
Phase error: ≤40′
Response time: ≤20 ms
Linearity: ≤1 %FS
Altitude: 2000 m
Dielectric strength: 10 kVAC/min
Insulation resistance: 1000 MΩ @ DC 500V
Operating temperature: -40 to +70 °C
Storage temperature: -40 to +85 °C


Ordering Code Includes

  • Rogowski coil
  • Rogowski signal converter → 5A
  • AC/DC power supply

Installation Guide

  1. Switch off all power sources to this device and the equipment in which it is installed before performing any work.
  2. Always use a suitable and approved voltage measuring device to confirm that all power is off.
  3. Turn the gray locking sleeve counterclockwise to disconnect the connector. Open the coil.
  4. Place the Rogowski coil around the conductor and bring the ends together.
  5. Reinsert the connector into the coupling and turn the sleeve clockwise until securely fastened.
  6. Connect the signal outputs to your integrator, oscilloscope, measuring instrument, or power analyzer to start real-time current measurements.
  7. Restore power to the panel.

Important: Secondary sides of current transformers must always be short-circuited or connected to a burden.

3 other products in the same category :

IN-LO-RS-1000-05A

IN-LO-RS-1000-05A

669,09 €

IN-LO-RS-2000-05A

IN-LO-RS-2000-05A

683,64 €

IN-LO-RS-3000-05A

IN-LO-RS-3000-05A

683,64 €